2 Zones Slave Fire Alarm Control Panel MINI Fire Alarm Control System Conventional Security Host Fire Controller
General Introduction
The panel range is designed to meet the requirements of EN54 Parts 2 & 4.
Product Features
The panels have the following key features: · 2 conventional input zones. · 1 notification appliance circuits (NAC) with built-in synchronization for ANSI 3.41and Gentex. · The panel comes with a 2 amp power supply. · Dedicated alarm and trouble relays. · 1 RS485 can be able to connect the other panel. · Housed in a 205mm W x 258mm H x 81mm D metal enclosure. · Enclosure supports two 12V, 4Ah backup batteries.
Technical Specifications
Primary AC : 120VAC 50/60 Hz Power supply rating 240VAC 50/60 Hz
Power supply rating : 2 Amps @ 24VDC
Maximum Battery Charging Current : 0.98 Amps @ 26VDC
Initiating Device Circuits 2 Zones: Alarm Zone 2 Normal Initiating Operating Voltage: 23VDC, Maximum 26VDC, regulated Normal Quiescent Current (normal status): <50mA Alarm Current (not include the others): <150 mA Short Circuit Initiating Current (per zone): 35mA Maximum Maximum Initiating Resistance (per zone): 10 ohms Initiating End-of-Line Resistor: 4K7 ohms, 1/2W 5% Standby Detector Current (per zone):4mA maximum Maximum Detector Count (per zone):30 detectors Initiating Cabling Type:18AWG Twisted Shielded pair (14 – 18 AWG) Detector Base Impedance:430 ohms Notification Appliance Circuits:1 NACs, Special Application Maximum NAC Current Rating:1 Amp maximum per circuit NAC Operating Voltage:26VDC Nominal, 30VDC Maximum NAC End-of-line Resistor:1N4007 Diode FAULT Relay rating:2A & 30VAC, resistive Alarm( Auxiliary ) Relay rating:2A & 30VAC, resistive Slave alarm panel:LED display only
|
|